UPS Sapotec Delta series DPS II 300kVA
300kVA 3/3 phase cable entry
Delta's Ultron DPS is a three-phase, double-conversion UPS with an IGBT rectifier. Featuring advanced topology with three-stage inverters and three-phase power factor correction, the Ultron DPS offers industry-leading performance with up to 96% AC-AC efficiency, an input power factor of > 0.99, an output power factor of 0.9, and a low input THD of < 3%.
Nominal Power 300kVA/270kW
Input
Nominal voltage 380/220 V, 400/230 V, 415/240 V (3-phasig, 4-adrig + G)
Voltage range 242~477 Vac*1
Current THDi: < 3%*2
Power factor: > 0.99
Frequency: 50/60 ± 5 Hz
Output
Voltage: 380/220 V, 400/230 V, 415/240 V (3-phase, 4-adrig + G)
Output power factor: 0,9
Voltage THDi: = 1.5 % (lineare Last)
Voltage regulation ±1% (static)
Frequency: 50/60 ± 0.05 Hz
Overload capacity = 125%: 10 minutes ; = 150%: 1 minute
Interfaces:
Standard: RS232 x 1, Chip card slot x 2, potential-free output contact x 6,
Potential-free Input contact x 7, (potential-free Input contact,
REPO x 1, External battery status detection x 1, Parallelport x 2, USB-Port x 1
Display
Mimic LCD more languages and LED indicators
Conformity:
Security & EMV: EN 62040-1; CE; IEC 61000-4; IEC 62040-2
More details:
Parallele redundancy & Erweiterung: ja, until 8 systems
Shutdown: yes, local and remote
Event log: 500 entries
Efficiency:
AC-AC: 94-96 % between half and full load
92-93 % between 20% and 30% load
ECO-Mode: bis 99 %
Environment:
Operating temperature: up to 40°C
Relative humidity: up to 95% (non condensing)
Audible sound level (at 1m distance): <73dB(A)
Details:
Dimensions: (WxDxH) 1600x865x1950 mm
Weight: 1200 kg
High reliability
Low costs
High flexibility
Easy maintenance
Intelligent battery management